The EBW1 series intelligent air circuit breakers (ACB) are designed for AC 50Hz power systems with rated voltages of 400V and 690V, and rated currents ranging from 630A to 6300A.
They are mainly used for power distribution and for protecting circuits and electrical equipment from overload, short circuit, undervoltage, and single-phase grounding faults.
Equipped with an intelligent trip unit, the EBW1 ACB provides precise and selective protection, helping to prevent unnecessary power outages and ensuring a stable and reliable power supply.
This series fully complies with IEC 60947-1 and IEC 60947-2 standards.
Ambient temperature: -5°C to +40°C (average temperature within 24 hours not exceeding +35°C)
Altitude: ≤2000 m
Pollution degree: Class 3
Humidity: Relative humidity should not exceed 50% at +40°C; higher humidity levels are permissible at lower temperatures (up to 90% at +20°C).
When condensation occurs, appropriate protective measures should be taken.
Main technical parameter
Type | EBW1-2000 | EBW1-3200 | EBW1-6300 | ||
Pole | 3P, 4P | 3P, 4P | 3P, 4P | ||
Using category | B | B | B | ||
Rated current In | A | 630, 800, 1000 1250, 1600, 2000 | 2000, 2500, 3000 | 4000, 5000, 6300 | |
Rated frequency | Hz | 50 | 50 | 50 | |
Rated operation voltage Ue | V | 400, 690 | 400, 690 | 400, 690 | |
Rated insulation voltage Ui | V | 800 | 800 | 800 | |
Arcing distance | mm | 0 | 0 | 0 | |
Rated impulse withstanding voltage Uimp | V | 8000 | 8000 | 8000 | |
Rated operation short circuit breaking capacity Ics (O-t-CO) | 400V | kA | 50 | 80 | 100 |
690V | kA | 40 | 50 | 75 | |
Rated limiting short circuit breaking capacity Icu (O-t-CO) | 400V | kA | 80 | 100 | 120 |
690V | kA | 50 | 65 | 85 | |
Rated short circuit closing capacity Icm | 400V | kA | 176 | 220 | 264 |
690V | kA | 105 | 143 | 187 | |
Rated short time withstanding current Icw (O-t-CO, AC400V 0.4S) | 400V | kA | 50 | 65 | 85 |
Operation life | Per hour | times | 20 | 20 | 10 |
Electrical | times | 1000 | 500 | 500 | |
Mechanical | times | 10000 | 5000 | 5000 | |
Full breaking time | ms | 20~30 | 20~30 | 20~30 | |
Full closing time | ms | 55~70 | 55~70 | 55~70 | |
Power consumption | 3P | W | 360 | 1200 | 2000 |
4P | W | 450 | 1750 | 2300 | |
Resistance of each pole | Fixed type | μΩ | 11 | 9 | - |
Draw out type | μΩ | 20 | 14 | 10 | |
Dimensions (L×W×H) | 3P fixed type | mm | 362×323×402 | 422×323×402 | |
3P draw out type | mm | 375×461×452 | 435×471×452 | ||
4P fixed type | mm | 457×323×402 | 537×323×402 | ||
4P draw out type | mm | 470×461×452 | 550×471×452 | ||
Approximate weight | 3P fixed type | kg | 41 | 55 | |
3P draw out type | kg | 71 | 95 | 245 | |
4P fixed type | kg | 51.5 | 65 | - | |
4P draw out type | kg | 86 | 115 | 260 |
Overload protection data
Overload protection | EBW1-2000~6300 | |
Adjust scope Ir1 | (0.4-1)In (pole difference 2%) | |
1.05 Ir1 | h | ≥2h non-tripping |
1.3 Ir1 | h | ≤1h tripping |
Delay time tr1 when current is 2.0 In | s | 3.32, 5.32, 8.00, 13.3, 20, 26.6, 33.3, 45, 60, 93.3, 133, 200, 266, 333, 400, 433 |
Delay time tr1 when current is 3.0 In | s | 1.25, 2, 3.5, 7.5, 10, 12.5, 16.8, 22.5, 35, 50, 75, 100, 125, 150, 162 |
Accuracy | % | ±10 |
Short circuit, short time delay | ||
Adjust scope Ir1 Ir2 | (0.4-15)In (pole difference 2%) | |
Delay time tr2 | ms | 100, 200, 300, 400 |
Accuracy | % | ±10 |
Electrical accessories
Under-voltage release | Rated working voltage Ue(V) | AC400 AC230 |
Acting voltage (V) | (0.35~0.7) Ue | |
Reliable close voltage (V) | (0.85~1.1) Ue | |
Non close voltage (V) | ≤0.335Ue | |
Power loss | 12VA (EBW1-1000 5VA) | |
Shunt release | Rated control power voltage Us(V) | AC400 AC230 DC220 DC110 |
Acting voltage (V) | (0.7~1.1) Ue | |
Open time | 40VA 40W (EBW1-1000 5VA) | |
Power loss | less than 30ms | |
Close electromagnetic iron | Rated control power voltage Us(V) | AC400 AC230 DC220 DC110 |
Acting voltage (V) | (0.85~1.1) Ue | |
Open time | 40VA 40W (EBW1-1000 5VA) | |
Power loss | less than 70ms | |
Motor operating device | Rated control power voltage Us(V) | AC400 AC230 DC220 DC110 |
Acting voltage (V) | (0.85~1.1) Ue | |
Open time | 40VA 40W (EBW1-1000 5VA) | |
Power loss | less than 5s |